4-20 mA Current Loop
Analog signaling method in which 4 mA represents the live zero and 20 mA represents full scale.
The Explain card
- Plain English
- A current loop sends a measurement as a current that varies between 4 and 20 mA. Four means the bottom of the range and twenty means the top.
- Example
- A flow meter spanned for zero to 100 gallons per minute puts out 12 mA at 50 gallons per minute. The input card reads 12 mA and the program scales it to 50.
- Why it matters
- Current holds up over a long cable in a way voltage cannot, so loops survive hundreds of feet of conduit. The live zero at 4 mA means a broken wire reads 0 mA and can be flagged as a fault rather than as an empty tank.
- Hook
- Four is zero, and zero is a broken wire.
Word knowledge
How the word is built, where it came from, and what it sits beside in memory.
In a sentence
The technician connects the pressure transmitter's 4-20 mA Current Loop to the PLC analog input and verifies the reading during commissioning.
Why these words
- 4-20 Hindu-Arabic numerals joined by modern range notation states the conventional span in compact numerical form
- mA SI-style symbol using Latin milli, thousand, and A for ampere identifies milliamperes as the measurement unit
- current Latin currere, to run, through Anglo-French curant names the electrical quantity used by the signal
- loop late Middle English loop, a doubled or closed path, of uncertain origin describes the closed circuit through the connected devices
Where it came from
- Origin
- English instrumentation coinage combining numerical range notation, the electrical unit symbol mA, and the established phrase current loop
- Entered the language
- 1950s
- What changed
- General words for flowing electricity and a closed path became a fixed industrial-instrumentation label, with the numerical prefix distinguishing one standard from other loop formats.
How it is spelled
- Pattern
- A hyphen joins the numerical endpoints.
- Pattern
- The SI prefix m remains lowercase while A remains uppercase because ampere is named after André-Marie Ampère.
- Pattern
- A space separates the numerical range from the unit symbol.
- Breaks the pattern
- The unit symbol mA is case-sensitive and has no period or plural ending.
Spelled like
- 0-10 V signal
- 3-15 psi signal
- 1-5 V signal
Broken into chunks
-
4-20
- 0-10 V
- 3-15 psi
-
mA
- µA
- kA
-
current
- concurrent
- current-limiting
-
loop
- closed-loop
- loopback
What it sits beside
Same subject
- analog input module
- loop-powered transmitter
- signal isolator
- loop calibrator
- shielded twisted pair
Same shape
- 0-10 V signal
- 1-5 V signal
- 3-15 psi signal
industrial analog signal formats
- 4-20 mA Current Loop
- 0-10 V signal
- 3-15 psi signal
current-loop equipment
- pressure transmitter
- PLC analog input
- loop power supply
- loop isolator
Where it sits in the deck
Phase 2: PLC I/O and Field Signals
Where the controller meets the machine: discrete and analog signals, the wiring conventions behind them, and the field devices that send them.