Industrial Engineer · phase 14 of 16

DC Bus Overvoltage

Trip caused when DC-link voltage rises above its safe limit, often during rapid deceleration or high line voltage.

The Explain card

Plain English
A bus overvoltage trip fires when the DC link rises past its safe limit. The usual cause is the motor regenerating faster than the drive can absorb, and the other one is a high incoming line.
Example
A fan is set to decelerate in five seconds. The bus climbs past 800 volts on the way down and the drive trips, leaving the fan to coast.
Why it matters
It is the most common fault on drives with fast ramps and heavy loads. The cures are a longer deceleration, stall prevention, a braking resistor, or a regenerative front end, and the fault history tells you whether it happens on stops or at random.
Hook
The energy came back and had nowhere to go.

Where it sits in the deck

Phase 14: VFD Safety, Faults, and Diagnostics

What a drive does when it trips, what the fault codes are telling you, and how safe torque off stops the motor without killing the panel.